Conventional 4-zone fire control panel supporting up to 32 detectors or manual call points per zone. It has a durable plastic housing and shows all indications and commands on the front, in line with the requirements laid down by law. Indications for fire alarm, fault, siren disabled, silence mode, zones disabled and test. Secondary power supply battery 12 VDC / 7 Ah. Certified to the EN 54-2 and EN 54-4 standards.
Technical data 43CPC004EN
- ERACLE conventional fire control panel with 4 detection lines, each with up to 32 Comelit detectors or call points.
- Uninterrupted line monitoring through end-of-line impedance, with Walk Test capability.
- Access levels protected by key, mechanical key at level 2.
- Fault relay and alarm relay with contacts rated 3 A at 120 VAC or 3 A at 60 VDC.
- Two monitored outputs with a maximum current of 0.3 A each, siren circuit 0.5 A at 24 VDC with a 0.5 A PTC fuse.
- Backup supply from 1 battery 12 VDC 7 Ah with a 2 A fuse. The battery is not supplied.
- Mains absorption 50 mA, up to 0.7 A for connected devices with a charged battery.
- Zone currents: 2–10 mA in normal mode, 10–110 mA in alarm, above 110 mA on short circuit and 0–2 mA on fault or open circuit.
- Plastic case, 2,100 g without battery.
- Operation from -5 to 40 °C with humidity up to 96% at 40 °C, storage from -20 to 60 °C.
Product code: 43CPC004EN. See also in the Conventional Fire Detection System category: CONVENTIONAL FIRE CONTROL PANEL 8 ZONES and CONVENTIONAL BASE WITH DIODE.